Lichfield Fire & Safety Equipment FZE - LIFECO - | E-Showroom
Lichfield Fire & Safety Equipment FZE - LIFECO - | E-Showroom
The LE-FN-LCD-N type LCD network annunciator is designed to be used with the Fire NET analog addressable system. It allows for remote access, monitoring & control of the Fire NET system throughout the building. The LE-FN-LCD-N is a true network annunciator that can access, monitor & control any or all Fire NET panels in the network. Each LE-FNLCD-N is completely independent. The highly intuitive user interface and 320-character LCD display of the LE-FN-LCD-N is exactly the same as the Fire NET panel. In addition to routing any panel in the network to the LE-FN-LCD-N, every event category within each panel can also be individually routed, as well as routing of all remote control functions (reset, alarm silence, re-sound alarm) from individual panels. The LE-FN-LCD-N supports the same RS485expansion port as the Fire NET panel, allowing for Fire NET expansion boards and accessories to be connected to the network annunciator. The LE-FN-LCD-N also has (4) output relays for fire, supervisory, trouble & auxiliary. The relays are programmable (except supervisory). Security is established by the use of a password or firefighters enable key. Designed to be aesthetically pleasing, the LE-FN-LCD-N is available in charcoal grey or red and can be surface or flush mounted using a standard trim ring kit.
• UL 864 9th edition Listed
• 320 character liquid crystal display (8 line x 40 character)
• LED indicators for Fire, Supervisory Alarm, Pre-Alarm, Fire Output Active, Power On, On Test, Panel Sounder Silenced, Delay Active, More Events, Point Bypassed, General Trouble, Power Trouble, System Trouble & NAC Trouble
• Dual RS485 ports for primary fire network
• RS485 slave bus for expansion - up to
31 LE-FN-4127-IO boards or up to 15 LE-FN-LCD-S serial annunciators and up to16 LE-FN-4127-IO boards
• 2 built-in RS-232 interfaces for programming via a PC and serial printer interface
• 4 on board programmable Form C elays rated at 1 Amp at 30VDC (Fire, Supervisory, Trouble & Auxiliary)
•Same controls as the FireNET fire panel (Reset, Panel Sounder Silence, Lamp Test, Alarm Silence, Re-sound Alarm, Fire Drill, Programmable Function, More Events, More Fire Events, Enter & Exit)
• Local piezo sounder for event notification
• Supports user codes & firefighter key to enable access & controls
• Powered by FireNET Aux 24VDC or UL fire listed Aux. 24VDC supply
• Available in red or charcoal, and can be surface or flush mounted (using trim ring)
• True network annunciator, any or all panels can be routed to the LE-FN-LCD-N.
In addition, each event category can be individually routed to the LE-FN-LCD-N
• Up to (64) FireNET panels & LE-FN-LCDN’s can be networked together in any combination
• 500mA of auxiliary power available rated at 24VDC
• Auto-learn feature
• Built-in help & alarm information screens
• Fire drill function
• Each LE-FN-LCD-N is completely independent
• Supports up to (31) LE-FN-4127-IO boards on RS485 expansion port
• The LE-FN-LCD-N can be configured to remote reset, silence, resound, any or all panels on the network in any combination.